Managing Dissolved Oxygen in Activated Sludge Plants

Specify Alternate Text

Sustaining optimal dissolved oxygen levels in activated sludge plants is necessary for biological treatment of organic material and ammonia. While raw wastewater often contains some amounts of oxygen, aeration systems can increase dissolved oxygen (DO), mixing, and the suspension of microbes through mechanical agitation or diffused aeration. Aerobic microorganisms use this oxygen to breakdown organic waste into inorganic byproducts. The amount of dissolved oxygen consumed by microbes during biological treatment is referred to as biochemical oxygen demand (BOD). According to an article by Triplepoint Water, approximately 1.5 pounds of oxygen is consumed for every pound of BOD oxidized. To oxidize one pound of ammonia, that value increases to 4.57 pounds of oxygen. Most plants aim to maintain around 2 mg/L of DO which allows microbes contained within the center of floc to receive oxygen.

Wastewater operators should regularly monitor oxygen availability in the form of dissolved oxygen. Insufficient oxygen levels will allow aerobic and nitrifying microbes to die and floc to break up. At DO concentrations under 1 mg/L, the potential for filamentous growth increases. On the other end of the spectrum, too much oxygen increases power consumption and, at very high levels, inhibits settling. Research has estimated that aeration can use up to 45 to 75% of a treatment facility’s overall electricity use. With an online DO analyzer equipped to automated controls, the EPA reports that energy costs can be reduced by as much as 50%.

Where and when an operator samples for DO will be determined by the requirements written in the facility’s National Pollutant Discharge Elimination System (NPDES) permit and basic process control. To compare dissolved oxygen levels throughout the day, samples should be collected at the same location. The Ohio EPA’s Activated Sludge Process Control and Troubleshooting Chart Methodology recommends that systems sample within 1-2 feet of the surface water near the discharge of the aeration tank into the clarifier. By collecting multiple samples in the same location throughout the week, operators can reliably determine if DO concentrations are sufficient for treatment while developing a DO profile. In addition, measuring DO at multiple depths and locations in the aeration tank can help find dead spots.  

To supply adequate DO, the Ohio EPA manual includes how to determine blower runtime based on organic loading and system design. We should  still note that temperature, pressure, and salinity can all influence the solubility of oxygen. Additional sampling locations can include the raw wastewater, aerobic/ anaerobic digester, and final effluent. Final effluent with high dissolved oxygen can cause eutrophication in the receiving waters, however low DO can harm aquatic organisms. Some permits set a minimum DO level for effluent to ensure aquatic organisms have the necessary oxygen levels to sustain life.

While every technique and tool has its strengths and weaknesses, operators can measure DO through a Winkler Titration test (see Michigan DEQ Laboratory Training Manual pg.91), electrochemical sensor, or optic sensor. The two sensors mentioned can be purchased as portable handheld meters or stationary devices. For automated blower control and continuous sampling, an online sensor is used. For NPDES compliance monitoring, measurements must be taken through an EPA approved method at the frequency specified in the permit.

When using any DO sensor, the EPA’s Field Measurement of Dissolved Oxygen (SESDPROC-106) procedures require that the equipment be well maintained and operated per manufacturer instructions. Upon initial purchase, probes should be inspected, calibrated, and verified for accuracy. During each additional use the instrument should be calibrated and inspected again. The EPA recommends checking instrument calibration and linearity using at least three dissolved oxygen standards annually. All maintenance and sampling activities should be documented in a logbook per NPDES requirements. Any time a measurement is taken, the temperature of the water and any notable wastewater conditions should also be recorded in the logbook. 

Dissolved oxygen is a frequently monitored parameter in wastewater treatment systems. Operators should have a firm understanding of how dissolved oxygen is involved in wastewater processes and how they can manage DO to achieve compliance. Check out our online document library to find useful resources to learn more.

Nocardia Foam in Activated Sludge Systems

Specify Alternate Text

Nocardioforms are filamentous, Gram positive actinomycete bacteria that can cause persistent and excessive foaming in activated sludge plants during the summertime. There are nine main genus of nocardioforms. Two of these genera are involved in activated sludge foaming, Rhodococcus and Nocardia with the latter being the better known troublemaker. How to best control Nocardia foam is a highly debated topic.

Nocardioforms are known for their branch-like hyphae that extend from the cell wall similar to the hyphae found in fungi. These branches link together with other filaments and floc. Simple and complex organic material make up their diet which includes fats, oils, and grease (FOG). Nocardioforms are slow growing and utilize the aerobic conditions established by an aeration tank. These actinomycetes generally have difficulty out-competing other wastewater microorganisms, but once established they're a handful to remove.

Present in lower concentrations, Nocardia help to stabilize floc structure. The bacteria can rapidly breakdown biochemical oxygen demand (BOD) which can be beneficial to high strength wastewater. In higher concentrations, Nocardia can rip the floc apart and swiftly breakdown BOD starving out floc forming bacteria. The dense, brown foam that accompanies an outbreak forms when filaments float to the surface as a result of their low-density fatty acid membrane and the waxy, hydrophobic biosurfactant that coats their bodies. Bubbles from the aeration system can also help the filaments to float. Unlike Microthrix, nocardioforms are not often associated with sludge bulking.

Unfortunately, the conditions required for a nocardioform outbreak are still debated. In general, any change in temperature, pH, dissolved oxygen (DO), solids concentration, or nutrients might spur an outbreak. It’s believed that nocardioforms will be most favored under warm temperatures with a high concentration of FOG, low food to mass (F/M) ratio, and/or a high mean cell residence time (MCRT). Since nocardioforms grow slowly, they need ample time to proliferate, and under low F/M their larger surface area helps to secure nutrients easily. Some people theorize that anaerobic conditions in parts of the aeration tank or surfactants can encourage Nocardia growth as well.

Before deciding on a treatment solution, it helps to confirm that you are dealing with nocardioforms and not some other filament. Just because your foam is brown, doesn’t ensure that Nocardia is the culprit. Toni Glymph has developed a manual that describes how to identify filaments under the microscope. Nocardia is both Gram positive and Neisser positive, but after reading his guide you’ll find that only a Gram stain is really required for identification.

Treatment solutions for nocardioform foam are also highly debated. Using a high volume water spray will temporarily break down the foam, but be prepared for its return. A better solution is to skim off excess foam so the bacteria is not recycled back into the system. Chlorination is not highly recommended. The branching Nocardia filaments prevent sufficient disinfectant contact while healthy floc bacteria are killed. Many companies promote defoaming products, but the interlocking filaments are often too stable for these chemicals as well. Most resources recommend reducing your MCRT to under 8 days while increasing (F/M). Wastewater technician, Jeff Crowther, lists three of his own treatment recommendations on page 10 of the H2Oregon Springs 2016 Newsletter. Solids wasting may be the most common control method. Operators should learn about the life cycle of Nocardia to maintain a system that avoids future foaming incidents.

Preventing a Bloodworm Invasion

Specify Alternate Text

Midge fly infestations can pose considerable challenges for activated sludge systems and lagoons. Also known as Chironomids or bloodworms in their larvae stage, these insects resemble mosquitos without the blood sucking proboscis. Adult males can be distinguished from females based on their feather like antennae. After dormancy in the winter, midge flies emerge in the summer ready to lay between 100 and 3,000 eggs per female.

Though midge flies do not suck blood like mosquitos, they disrupt communities in other ways. Swarms annoy both local residents and operators by flying into unsuspecting mouths and flooding outdoor lighting. A study by Selden et al. (2013) found that wastewater operators can develop allergic reactions from midge fly exposure. Chironomids can also cause quite a startle to the public when bright red larvae make their way into drinking water systems.

When it comes to maintaining treatment systems, wastewater operators may be most concerned with the larvae stage of midge flies. Their sticky red bodies cling to suspended solids encasing them in a cocoon of decaying organic matter. Under the protection of these cocoons, they can consume considerable amounts of sludge, bacteria flocc, and nitrifying bacteria. An infestation will cause sludge clumping, rising solids, or foaming issues. In one small town a bloodworm invasion wreaked havoc on an activated sludge plant over a single weekend. The wastewater operator found sticky clumps of eggs had congested the system’s pumps while larvae had eaten away at his mixed liquor suspended solids (MLSS).

Facultative lagoons and secondary clarifiers are a favored breeding ground for these pests. Midge flies prefer to lay their eggs in still, high-nutrient water with fixed media, floating scum, or algae. Once the eggs hatch, larvae will likely sink to the bottom to feed on organic matter and sludge. The hemoglobin that gives bloodworms their red color also allows them to live in low dissolved oxygen (DO) conditions.

To avoid bloodworm infestations, operators should focus on encouraging circulation and limiting food sources. Systems can start midge fly control with mixing, limiting surface scum and algae, installing bug zappers, attracting bats and swallows, or turning off lights at night. Introducing a predatory fish can also help. Lagoon operators can encourage circulation by cutting back overgrown vegetation. Any dead spots in circulation should be addressed. When these methods don’t work, some systems will use larvicides and chemical agents as a last resort. Operators should check that the control methods they’ve selected are approved by their local regulatory authorities before use.

When summer starts make sure your treatment system is kept clean and free of obstructions to circulation. With good preventative maintenance, you can spare yourself the nightmares of a bloodworm invasion.